Cisco CX-FEIP-1TX= Installation and con?guration Guia do Utilizador Página 397

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 396
PTP 800 Series User Guide Installing antennas and IRFUs
phn-2513_004v000 (Oct 2012)
5-75
Safety requirements for grounding:
It is very important that the path of lowest resistance goes directly to the main ground
point.
The ground conductor resistance needs to be less than 0.5 Ohm.
Do not connect other equipment to the same grounding cable as the IRFU. Each piece of
equipment at the site should have a separate grounding cable to a common very low
resistance main ground point.
Connect the equipment directly to the DC supply system grounding electrode conductor
or to a bonding jumper from a grounding terminal bar, or bus to which the DC supply
grounding electrode is connected.
Provide fusing according to Local and National Electrical Codes. Fuse rating must be: 4 A
for -48 V operation.
Vista de página 396
1 2 ... 392 393 394 395 396 397 398 399 400 401 402 ... 647 648

Comentários a estes Manuais

Sem comentários