Monitor the Temperature
1. Launch the Chassis Manager by entering the IP address of the InfiniBand switch into your web
browser.
2. Press the Enter key.
3. The Device Rear View and the Device Front View appear.
4. Click open the Chassis file in the left-navigation tree.
The individual components appear beneath the Chassis menu.
Click Sensors in the left-navigation tree.
The Sensors window appears.
Figure 5-17: Chassis Manager Sensors Window
5. Verify that the sensor is Up by checking the Current Status column.
6. Compare the Current Temp (c) column to the Alarm Temp and Shutdown Temp columns.
The Current Temp should be lower than the Alarm Temp. The Shutdown Temp indicates the
degree in celsius (at sea level) at which the switch will reboot.
Each slot is monitored with individual sensors. The Alarm and Shutdown temperatures vary
depending on the slot.